Product Introduction

The HK-MXB-0320 in the MX-Basic series is an EtherCAT industrial Ethernet bus interface that integrates a mixed I/O module for digital input and output. It can provide an ideal 16 channel industrial field 24V NPN/PNP digital logic input signal for higher-level EtherCAT master station controllers, and provide safety protection for current limiting and electrical isolation of the captured signals.
At the same time, HK-MXB-0320 can also convert the command signal issued by the main station controller into a 16 channel NPN/PNP industrial 24V digital logic signal output, with a maximum driving current of 0.5A/CH, which can be used to drive relays, indicator lights, and digital logic signals.
HK-MXB-0320 is divided into two models: HK-MXB-0320-1100 and HK-MXB-0320-2200. HK-MXB-0320-1100 is a PNP type 16 channel digital input and 16 channel digital output module, and HK-MXB-0320-2200 is an NPN type 16 channel digital input and 16 channel digital output module.
The 16 input and 16 output channels, EtherCAT communication interface, and power interface of HK-MXB-0320 all have corresponding LED indicators for quick observation and diagnosis of signal and command status.

2

Product Model

HK-MXB-0320-1100

HK-MXB-0320-2200

3

Product Parameters

Model Parameters

Name

MXB-0320-1100

MXB-0320-2200

Unit

Supply Voltage

24(-15 %/ +20 %)

24(-15 %/ +20 %)

VDC

Digital input signal
Number of input channels
Input ‘0’ voltage range
Input ‘1’ voltage range
Input current limit

PNP
16
0~7
10~24
Typical Value 2.3

NPN
16
16~24
0~13
Typical Value 2.3

*
*
V DC
V DC
mA

Digital output signal
Number of output channels
Output current
Reverse voltage protection
Short circuit and overcurrent protection
Load type

PNP
16
Max 0.5A/channel


resistance, inductance, lamp type

PNP
16
Max 0.5A/channel


resistance, inductance, lamp type

*
*
mA
*
*
*

Distributed clock (64bit)

Protect
Electrical isolation and withstand voltage
Protection level

*
500 (communication and on-site voltage)
IP20

*
500 (communication and on-site voltage)
IP20

*
V
*

Environment
Working temperature
Storage temperature
Relative humidity

*
0 ~﹢60
﹣25 ~﹢70
10 ~ 95

*
0 ~﹢60
﹣25 ~﹢70
10 ~ 95

*


%

Size
Weight

~112.2 x 125.4 x 51.4
~182

~112.2 x 125.4 x 51.4
~182

mm
g

Installation method
Installation clearance

35mm DIN rail
Upper and lower clearance 35

35mm DIN rail
Upper and lower clearance 35

*
mm

Product Characteristics and Applications

Product Characteristics

16 channel 24V NPN/PNP digital input
16 channel 24V NPN/PNP type 0.5A/CH output
Input current limiting protection
Output current limiting and short circuit protection
Bus communication fault indicator light
Pluggable terminal blocks
DIN35 rail installation

Appliactions

logical control
Bus data collection
distributed control
Distributed monitoring
Industrial robot
numerical control machine

✔ Interface Definition

 

Pin

Name

Direction

Introduction

1

Us 24V

I

Us communication part power supply 24V

2

Us 0V

I

Us communication part power supply 0V

3、4

Up 24V

I

Up on-site peripherals, load part power supply 24V

5、6

Up 0V

I

Up on-site peripherals, load part power supply 0V

7

PE

Ground, shielding

 

✔ Indicator Light

 

Mark

Object

Color

Introduction

Us

Us Power Indicator Light

White

On: The power supply is normal

Up

Up Power Indicator Light

White

On: The power supply is normal

✔ Interface Definition

 

Pin

Name

Introduction

1

Tx+

EtherCAT data transmission, differential signal+

2

Tx-

EtherCAT data transmission, differential signal-

3

Rx+

EtherCAT data reception, differential signal+

6

Rx-

EtherCAT data reception, differential signal-

4、5、7、8

not used

 

✔ Indicator Light

 

Mark

Object

Color

Introduction

ECAT RUN

EtherCAT status

Yellow

On: The device is in an operable state
Blinking for 1 second: in a ready state and not operable
Flashing for 0.5 seconds: in a safe state and cannot perform output operations

ECAT ERR

EtherCAT communication error

Yellow

On: Communication error with slave device

ECAT IN LinkACT

In port communication link status

Green

On: establish a link with the previous module
Flashing: Establishing communication with the previous module

ECAT OUT LinkACT

OUT port communication link status

Green

On: establish a link with the subsequent module
Flashing: Establishing communication with the downstream module

 

✔ Unit 1 Interface Definition

 

Pin

Name

Direcation

Introduction

1~16

DI 1~16

I

Digital signal input channels 1-16

COM 0V

COM 0V

O

The Up 0V power supply is used for the power supply of on-site digital input/output equipment

COM 24V

COM 24V

O

The Up 24V power supply is used for the power supply of on-site digital input/output equipment

 

✔ Unit 1 Indicator Light

 

Mark

Object

Color

Introduction

1~16

DI input channel 1~16

White

On: The input signal is valid

✔ Unit 2 Interface Definition

Pin

Name

Direcation

Introduction

1~16

DO 1~16

O

Digital signal output channels 1-16

COM 0V

Up 0V

O

The Up 0V power supply is used for the power supply of on-site digital input/output equipment

COM 24V

Up 24V

O

The Up 24V power supply is used for the power supply of on-site digital input/output equipment

✔ Unit 2 Indicator Light

Mark

Object

Color

Introduction

1~16

DO output channels 1~16

White

On: The output signal is valid